A4 Event Recorder; Event Records - GE Feeder Management Relay 750 Instruction Manual

Table of Contents

Advertisement

6.5 A4 EVENT RECORDER

6.5A4 EVENT RECORDER
PATH: ACTUAL VALUES
E128: March 16 1997
[ENTER] for more
6
The 750/760 has an event recorder which runs continuously, capturing and storing the last 128 events. All event recorder
information is stored in non-volatile memory so the information is maintained after losing relay control power. The last 128
events are displayed from newest to oldest event. Each event has a header message containing a summary of the event
that occurred. Each event is assigned an event number equal to the number of events that have occurred since the
recorder was cleared; the event number is incremented for each new event. Event recorder data can be cleared with the
RELAY SETUP
CLEAR DATA
6-16
Courtesy of NationalSwitchgear.com
A4 EVENT RECORDER
E001(128)
ð
ENTER
TIME OF EVENT:
ESCAPE
16:30:00.000
<Event_Type>:
ESCAPE
MESSAGE
<Cause_of_Event>
PHASE A CURRENT:
ESCAPE
MESSAGE
0 A
PHASE B CURRENT:
ESCAPE
MESSAGE
0 A
PHASE C CURRENT:
ESCAPE
MESSAGE
0 A
GND CURRENT:
ESCAPE
MESSAGE
0 A
SENSTV GND CURRENT:
ESCAPE
MESSAGE
0.00 A
LINE A-B VOLTAGE:
ESCAPE
MESSAGE
0.00 kV
LINE B-C VOLTAGE:
ESCAPE
MESSAGE
0.00 kV
LINE C-A VOLTAGE:
ESCAPE
MESSAGE
0.00 kV
LINE A-N VOLTAGE:
ESCAPE
MESSAGE
0.00 kV
LINE B-N VOLTAGE:
ESCAPE
MESSAGE
0.00 kV
LINE C-N VOLTAGE:
ESCAPE
MESSAGE
0.00 kV
SYSTEM FREQ:
ESCAPE
MESSAGE
0.00 Hz
SYNCHRO VOLTAGE:
ESCAPE
MESSAGE
0.00 kV
SYNCHRO FREQ:
ESCAPE
MESSAGE
0.00 Hz
A/I:
ESCAPE
0 μA
MESSAGE
CLEAR EVENT RECORDER DATA
750/760 Feeder Management Relay
Range: Time in format shown
Range: See Table 6–2: Event Types on page 6–17 and
Table 6–3: Cause of Events on page 6–18.
Range: 0 to 65535 A, 0 to 359° Lag
0° Lag
Range: 0 to 65535 A, 0 to 359° Lag
0° Lag
Range: 0 to 65535 A, 0 to 359° Lag
0° Lag
Range: 0 to 65535 A, 0 to 359° Lag
0° Lag
Range: 0 to 655.35 A, 0 to 359° Lag
0° Lag
Range: 0 to 65535 kV, 0 to 359° Lag
0° Lag
Range: 0 to 65535 kV, 0 to 359° Lag
0° Lag
Range: 0 to 65535 kV, 0 to 359° Lag
0° Lag
Range: 0 to 65535 kV, 0 to 359° Lag
0° Lag
Range: 0 to 65535 kV, 0 to 359° Lag
0° Lag
Range: 0 to 65535 kV, 0 to 359° Lag
0° Lag
Range: 0 to 90.00 Hz
Range: 0 to 65535 kV, 0 to 359° Lag
0° Lag
Range: 0 to 90.00 Hz
Range: 0 to 65535 Analog Input Units
setpoint.
6 ACTUAL VALUES

6.5.1 EVENT RECORDS

S1
GE Multilin

Advertisement

Table of Contents
loading

This manual is also suitable for:

Feeder management relay 760