3.2 ELECTRICAL
Ensure correct polarity on logic input connections and do not connect any logic input circuits to ground or
else relay hardware may be damaged.
CAUTION
External contacts can be connected to the relay's fourteen (14) logic inputs. As shown, these contacts can be either dry or
wet. It is also possible to use a combination of both contact types.
A dry contact has one side connected to Terminal C12. This is the +32 V DC voltage rail. The other side of the dry contact
is connected to the required logic input terminal. When a dry contact closes, a current of approximately 2 mA will flow
through the associated circuit.
A wet contact has one side connected to the positive terminal of an external DC power supply. The other side of this con-
tact is connected to the required logic input terminal. In addition, the negative side of the external source must be con-
3
nected to the relay's DC negative rail at Terminal D12. The maximum external source voltage for this arrangement is
300 V DC.
Terminals A1 (+) and A2 (–) are provided for the input of a current signal from a wide variety of transducer outputs - refer to
technical specifications for complete listing. This current signal can represent any external quantity, such as transformer
winding temperature, bus voltage, battery voltage, station service voltage, or transformer tap position. Be sure to observe
polarity markings for correct operation. Both terminals are clamped to within 36 V of ground with surge protection. As such,
common mode voltages should not exceed this limit. Shielded wire, with only one end of the shield grounded, is recom-
mended to minimize noise effects.
3-14
Courtesy of NationalSwitchgear.com
Dry Contact Connection
750/760 RELAY
+32 V DC
C12
C1
Logic Input 1
32 V DC
D12
DC Negative
Figure 3–17: DRY AND WET CONTACT CONNECTIONS
750/760 Feeder Management Relay
Wet Contact Connection
750/760 RELAY
C12
+32 V DC
Logic Input 1
C1
32 V DC
DC Negative
D12
3 INSTALLATION

3.2.7 LOGIC INPUTS

30 to 300 V DC
LOGICIN.CDR