8 COMMISSIONING TESTS
1.
Enter the following settings under the
FORCE OUTPUT RELAYS FUNCTION
FORCE 1 TRIP RELAY
FORCE 2 CLOSE RELAY
FORCE 3 AUXILIARY RELAY
FORCE 4 AUXILIARY RELAY
FORCE 5 AUXILIARY RELAY
FORCE 6 AUXILIARY RELAY
FORCE 7 AUXILIARY RELAY
FORCE 8 SELF-TEST RELAY
FORCE SOLID STATE OUTPUT
2.
Using a multimeter, check that all output relays are de-energized (i.e. N.O. contacts open, N.C. contacts closed).
3.
Make the following setting change:
4.
Check that the Trip output is energized (i.e. N.O. contacts closed), and the Trip LED is illuminated.
5.
Make the following setting change:
6.
Repeat Steps 3 through 5 for Output Relays 2 through 8 inclusive.
7.
Observing polarity, connect a minimum 5 V DC source in series with a limiting resistor that will permit a minimum cur-
rent of 100 mA, in series with the Solid State output. Observing polarity, connect a DC voltmeter across the limiting
resistor. Check there is no voltage displayed on the voltmeter.
8.
Change setting to:
9.
Check that a voltage has appeared on the voltmeter. Turn off the source and disconnect the test wiring.
10. Change setting to:
11. Change setting to:
GE Multilin
Courtesy of NationalSwitchgear.com
S8 TESTING
: "Enabled"
: "De-energized"
: "De-energized"
: "De-energized"
: "De-energized"
: "De-energized"
: "De-energized"
: "De-energized"
: "De-energized"
: "De-energized"
S8 TESTING
S8 TESTING
S8 TESTING

OUTPUT RELAYS

S8 TESTING
OUTPUT RELAYS
S8 TESTING
OUTPUT RELAYS
750/760 Feeder Management Relay
subheading:
OUTPUT RELAYS
OUTPUT RELAYS
FORCE 1 TRIP RELAY
OUTPUT RELAYS
FORCE 1 TRIP RELAY
FORCE SOLID STATE OUTPUT
FORCE SOLID STATE OUTPUT
FORCE OUTPUT RELAYS FUNCTION
8.2 INPUTS/OUTPUTS
8.2.3 OUTPUT RELAYS
: "Energized".
: "De-energized".
: "Energized".
: "De-energized".
: "Disabled".
8
8-9