A1 Status; Virtual Inputs; Hardware Inputs - GE Feeder Management Relay 750 Instruction Manual

Table of Contents

Advertisement

6 ACTUAL VALUES

6.2A1 STATUS

PATH: ACTUAL VALUES

VIRTUAL INPUTS

[ENTER] for more
The state of all active virtual inputs as well as the ability to set their state is displayed here. In some applications, these dis-
plays can be used instead of panel switches for controlling operations within the relay. The ability to have user defined
names for the inputs allows the operator interface to be easily understood. See Section 5.4: S3 Logic Inputs on page 5–19
for complete details on virtual inputs, their setpoints and application.
The first value displays how many logic inputs have a virtual condition selected as part of their asserted logic. The states of
Virtual Inputs 1 through 20 are displayed in this menu. The Logic Input 1 display heading is user-programmable. Note that
only "active" virtual inputs are displayed; active virtual inputs are those that have their
programmed to monitor the state of the virtual input. There are subsequent displays for the remaining virtual inputs.
PATH: ACTUAL VALUES

HARDWARE INPUTS

[ENTER] for more
These messages display the state of all hardware inputs. The top line in the last two values above reflect the names pro-
grammed in the
S6 MONITORING
respectively.
GE Multilin
Courtesy of NationalSwitchgear.com
A1 STATUS
VIRTUAL INPUTS
ð
ENTER
2 VIRTUAL INPUTS
ESCAPE
ARE ACTIVE
Logic Input 1
ESCAPE
MESSAGE
Off
A1 STATUS
HARDWARE INPUTS
ð
CONTACT 1 STATE:
ENTER
ESCAPE
Open
CONTACT 2 STATE:
ESCAPE
MESSAGE
Open
CONTACT 14 STATE:
ESCAPE
MESSAGE
Open
SETPOINT ACCESS
ESCAPE
MESSAGE
STATE: Restricted
Trip Coil Mon
ESCAPE
MESSAGE
STATE: Open
Close Coil Mon
ESCAPE
MESSAGE
STATE: Open
EQUIPMENT
750/760 Feeder Management Relay
Range: 0 to 20 Virtual Inputs
Range: On, Off
Reflects user-programmed name.
Range: Open, Closed
Range: Open, Closed
Range: Open, Closed
Range: Restricted, Allowed
Range: Open, Closed
Range: Open, Closed
COIL 1 MON
COIL 1 MON NAME
6.2 A1 STATUS
6.2.1 VIRTUAL INPUTS
setpoint
INPUT n ASSERTED LOGIC
6.2.2 HARDWARE INPUTS
and
setpoints,
COIL 2 MON NAME
6
6-5