5.7 S6 MONITORING
way, when a power factor condition starts the Power Factor 1 or 2 delay timer, if all three phase voltages fall below the 30%
threshold before the timer has timed-out, the element will reset without operating. A loss of voltage during any state will
return both Power Factor 1 and 2 to the reset state.
5
PATH: SETPOINTS
S6 MONITORING

FAULT LOCATOR

[ENTER] for more
5-76
Courtesy of NationalSwitchgear.com
Figure 5–39: POWER FACTOR LOGIC
FAULT LOCATOR
ð
ENTER
LENGTH OF FEEDER:
ESCAPE
0.1 km
UNITS OF LENGTH:
ESCAPE
MESSAGE
km
Zpos (RESISTIVE) OF
ESCAPE
Ω
MESSAGE
FEEDER: 0.01
Zpos (INDUCTIVE) OF
ESCAPE
Ω
MESSAGE
FEEDER: 0.01
Zzero (RESISTIVE) OF
ESCAPE
Ω
MESSAGE
FEEDER: 0.01
Zzero (INDUCTIVE) OF
ESCAPE
Ω
MESSAGE
FEEDER: 0.01
FAULT TYPE OUTPUT TO
ESCAPE
MESSAGE
RELAYS 4-7: Disabled
FAULT LOCATION AFTER
ESCAPE
MESSAGE
TRIP: Disabled
750/760 Feeder Management Relay
5.7.3 FAULT LOCATOR
Range: 0.1 to 99.9 km/Miles in steps of 0.1
Range: km, Miles
Ω
Range: 0.01 to 99.99
in steps of 0.01
Ω
Range: 0.01 to 99.99
in steps of 0.01
Ω
Range: 0.01 to 99.99
in steps of 0.01
Ω
Range: 0.01 to 99.99
in steps of 0.01
Range: Disabled, Enabled
Range: Disabled, Enabled
5 SETPOINTS