Auxiliary Relays - GE Feeder Management Relay 750 Instruction Manual

Table of Contents

Advertisement

5.5 S4 OUTPUT RELAYS
PATH: SETPOINTS
S4 OUTPUT RELAYS
3 AUX RELAY
[ENTER] for more
Figure 3–9: Typical Wiring Diagram on page 3–7 shows relay contacts with no control power applied. If the
setpoint is "De-energized", then the state of the relay contacts is as shown in the wiring diagram. If the
OPERATED STATE
non-operated state is "Energized", then the state of the relay contacts is opposite to that shown in the wiring diagram.
This
PULSED OUTPUT DWELL TIME
point determines the time interval that the pulsed contacts remain in the operated state.
5
5-30
Courtesy of NationalSwitchgear.com
3(7) AUX RELAY
ð
ENTER
RELAY 3 NAME:
ESCAPE
Auxiliary
RELAY 3 NON-OPERATED
ESCAPE
MESSAGE
STATE: De-energized
RELAY 3 OUTPUT TYPE:
ESCAPE
MESSAGE
Self-Resetting
PULSED OUTPUT DWELL
ESCAPE
MESSAGE
TIME:
0.1 s
setpoint is only displayed if the
Figure 5–3: OUTPUT RELAYS 3 TO 7 AUXILIARY LOGIC
750/760 Feeder Management Relay

5.5.4 AUXILIARY RELAYS

Range: 16 alphanumeric characters
Range: Energized, De-energized
Range: Self-Resetting, Latched, Pulsed
Range: 0.1 to 6000.0 s in steps of 0.1. Seen only if
RELAY 3(7) OUTPUT TYPE
is selected as "Pulsed". This set-
RELAY 3 OUTPUT TYPE
5 SETPOINTS
is "Pulsed"