7.6.2 Specification - 4XD and 4XV-Series
Type
Mains voltage
:
Frequency range
:
Emergency
:
power supply
Rated current
:
*6
@ 230 V AC
Rated current
:
*6
@ 24 V DC
Current
(1 kHz sinus / 1 min.)
:
*7
@ 24 V DC
*8
Output power
:
Technology
:
Transmission range
:
Input level
:
System input
:
impedance
Signal to noise ratio
:
Channel separation
:
Distortion factor
:
@ 1 kHz
Efficiency
:
Ambient
:
temperature
Storage
:
temperature
Humidity
:
Housing
:
Colour
:
Weight
:
Dimensions
:
(w x h x d)
Specification
:
*6
Rated current @ 33 % load
*7
Acc. EN 54-16 (laboratory test)
*8
Output power acc. EN 54-16.
For analogue amplifiers, the output power is generally used as the planning dimension.
This is not always possible for digital final stages. If there are no details relating to
amplifier/loudspeaker pairings for specific signals, a maximum of 50 % of the nominal power should
be used as the planning dimension.
FB 798663.GB0 / 05.19
4XD125B
4XD250B
21,5 V DC ... 28,5 V DC
1,13 A
2,2 A
9,44 A
18,6 A
26,5 A
53,5 A
4 x 125 W
4 x 250 W
20 ... 22 kHz
≥ 90 dB (A)
≥ 75 dB
≤ 0,3 %
approx. 9 kg
approx. 12 kg
483 x 44 x 400
mm (1HU)
Installation Instruction VARIODYN
4XD300
4XD500
230 V AC, +10% / -5%
50 ... 60 Hz
24 V DC
4,0 A
6,0 A
25,9 A
40,1 A
57,0 A
83,0 A
4 x 300 W
4 x 500 W
Class D
0 dBu
20 kOhm
≥ 80 %
-5 °C ... +55 °C
-10 °C ... +55 °C
up to 93 % rel. hum. (non-condensing)
Metal
grey, similar to RAL 7016
approx. 14,3 kg approx. 14,4 kg approx. 13,4 kg approx. 13,5 kg
483 x 88,4 x 390 mm (2 HU)
EN 54-4 and EN 54-16
®
D1 System
4XV300
---
4,0 A
---
---
4 x 300 W
20 Hz ... 20 kHz
≥ 97 dB (A)
≥ 83 dB
≤ 0,05 %
4XV500
---
6,0 A
---
---
4 x 500 W
71