Installation Instruction VARIODYN
7.4.2 DIP switch 4XD125B
Before commissioning, the DIP switch
OFF corresponds to the upper position and ON to the lower one.
•
Always power-down the Amplifier before setting the DIP switch
•
Use a non-metallic tool to change the settings of the DIP switch.
•
The DIP switch settings are read on Amplifier power-up.
1
1
2 3 4 5 6 7
ON
2
2 3 4 5 6 7
1
ON
3
1
2 3 4 5 6 7
ON
4
1
2 3 4 5 6 7
ON
5
1
2 3 4 5 6 7
ON
6
2 3 4 5 6 7
1
ON
7
2 3 4 5 6 7
1
ON
8
2 3 4 5 6 7
1
ON
64
®
D1 System
10
should be set to the desired function according to the table below. Here,
OFF:
Standard operation of the 4 x 125 watt final stages
8
(factory setting)
ON:
Switch setting not permitted
8
OFF:
Switch setting not permitted
ON:
Monitoring of the amplifier function (factory setting).
OFF:
Charging function for the connected batteries activated
8
(factory setting).
ON:
Battery charging function deactivated. Supply via an external
power supply.
8
OFF:
Monitoring of the connected batteries activated (factory setting).
ON:
No monitoring of the connected batteries (required if no batteries are
connected).
OFF:
Display of the audio signal strength via the two green LED <High/Low
8
channel> on the front side of the amplifier in the range -20 dB (low)
and -6 dB (high). Display function for the deviation from the nominal
value (factory setting).
ON:
Display of the audio signal strength via the two green LED <High/Low
channel> on the front side of the amplifier in the range -6 dB (low) and
-3 dB (high). Display function for the deviation from the nominal value.
8
OFF:
Setting of the attenuation factor 6 dB (factory setting).
ON:
Setting of the attenuation factor 20 dB.
OFF:
Reset display of the fault message automatically within 2 minutes after
8
a reset (factory setting).
ON:
Stored display of a fault message (resetting via I/F reset control input
required).
8
OFF:
CAN bus configuration (factory setting)
ON:
Switch setting not permitted
10
.