Honeywell HON R100NG Series User And Maintenance Manual page 52

Gas pressure regulator with pilot
Table of Contents

Advertisement

Threadlocker 
Tightening torques 
Maintaining the actuator 
assembly 
User manual for HON R100 gas pressure regulator with HON P095NG pilot 
Observe the threadlocker specifications below when following the instructions in this section: 
Part 
Diaphragm 
 
When screwing the actuator assembly's lower and upper covers, make sure to observe the 
following tightening torques: 
Nominal size 
Step 
38 
1" 
39 
38 
2" 
39 
38 
3" 
39 
38 
4" 
39 
38 
6" 
39 
38 
8" 
39 
 
Proceed as follows: 
Figure 
Threadlocker 
LOCTITE 243 
Screw specifications 
Qty 
UNC 3/8 ‐ 16 x 2 ½" 
UNC 1/2 ‐ 11 x 2 ½" 
UNC 1/2 ‐ 13 x 2 ¾" 
UNC 1/2 ‐ 13 x 2 ½" 
UNC 5/8 ‐ 11 x 3" 
UNC 5/8 ‐ 11 x 3 ¼" 
UNC 3/4 ‐ 10 x 4" 
UNC 3/4 ‐ 10 x 3 ¾" 
UNC 3/4 ‐ 10 x 4 ½" 
UN 1 ⅛ ‐ 8 x 5 ½" 
UNC 3/4 ‐ 10 x 4 ½" 
UN 1 ⅛ ‐ 8 x 5 ½" 
Step 
Description 
Unscrew the dome's nuts (1). 
Caution! The lid is spring‐loaded. Risk of 
injury due to bouncing up when the nuts 
are unscrewed. Hold the cover down when 
unscrewing the nuts. 
Remove the dome (1). 
 
Maintenance 
Step 
33 and 34 
Tightening torque 
4  30 Nm (22 ft lbs) 
12  120 Nm (89 ft lbs) 
4  80 Nm (59 ft lbs) 
16  120 Nm (89 ft lbs) 
6  120 Nm (89 ft lbs) 
16  230 Nm (170 ft lbs) 
6  160 Nm (118 ft lbs) 
16  400 Nm (295 ft lbs) 
8  160 Nm (118 ft lbs) 
16  1400 Nm (295 ft lbs) 
10  160 Nm (118 ft lbs) 
16  1400 Nm (295 ft lbs) 
52 

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hon p095ng seriesHon r100ngHon r100ng-foHon p095ng-mpHon p095ng-hp

Table of Contents