User manual for HON R100 gas pressure regulator with HON P095NG pilot 
The HON R100NG and HON R100NG‐FO actuator assembly versions feature the following 
ports: 
Figure 
Front: 
Back: 
 
 
HON R100NG 
 In a depressurized state, the compression 
spring will push the diaphragm upward so that 
the valve plate will close, creating a seal at the 
edge leading to the support cage (fail‐close). 
 The motorization pressure will produce a force 
component that acts on the diaphragm from 
above.   
 The force components are compared at the 
diaphragm.   
 If the motorization pressure is greater than the 
compression spring and outlet pressure acting 
from below, the valve plate will be pushed 
downward. This will open a corresponding gap 
between the inlet pressure and outlet pressure 
areas.   
 
No. 
Connection 
 
Motorization pressure 
Outlet pressure 
Inlet pressure 
 
Outlet pressure feedback 
 
 
HON R100NG‐FO 
 In a depressurized state, the compression 
spring will push the diaphragm downward, 
causing the valve plate to be pushed downward 
and opening a gap between the inlet pressure 
and outlet pressure areas (fail‐open). 
 The motorization pressure and the compres‐
sion spring will produce force components that 
act on the diaphragm from above. 
 The loading pressure will produce a force 
component that acts on the diaphragm from 
below. 
 The force components are compared at the 
diaphragm. 
 If the motorization pressure is greater than the 
loading pressure acting from below, the valve 
plate will seal off the inlett pressure areas from 
each other. 
 