Honeywell HON R100NG Series User And Maintenance Manual page 39

Gas pressure regulator with pilot
Table of Contents

Advertisement

Loosening the set screw 
on the pilot 
Adjusting the gas pres‐
sure regulator 
 
User manual for HON R100 gas pressure regulator with HON P095NG pilot 
Loosen the set screw on the pilot as follows: 
Figure 
 
Proceed as follows: 
Step 
Description 
Open the inlet shut‐off device. 
Slowly turn the pilot's set screw counterclockwise to screw it in until the outlet pressure 
almost matches the setpoint. 
Open the blowdown line's shut‐off device. 
Slowly screw in the pilot's set screw further until the outlet pressure matches the setpoint 
exactly. 
Now secure the set screw's position by tightening the hex nut. 
Important! Make sure that the set screw does not turn as you tighten the hex nut! 
Screw the cap back on. 
The regulating system has now been adjusted. Now slowly open the outlet shut‐off device 
to put the system into operation. 
Close the relief valve's shut‐off device. 
 
If problems occur during commissioning, please refer to the Malfunctions (see page 42) 
chapter for more information. 
Transport, installation and start‐up 
Step 
Description 
Unscrew the cap (1). 
Check whether the set screw (1), including 
the hex nut, has been loosened. If it has 
not, loosen it. 
 
39 

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hon p095ng seriesHon r100ngHon r100ng-foHon p095ng-mpHon p095ng-hp

Table of Contents