The unit maximum power consumption and cable lengths are as follows:
Unit Type
Maximum Power
Cross-Duct
(Transmitter +
Receiver)
Notes:
1.
The control room supply voltage is assumed to be +24V.
2.
All connections along the cable are sound and have zero resistance.
4.3.4 Unpacking
Carefully unpack the equipment, observing any instructions that may be printed on or contained
within the packaging.
Check the contents for damage and against the packing note for deficiencies. In the event of
damage or loss in transit, notify the carrier and Zellweger Analytics Limited or your local agent
immediately. The gas detector consists of the following items:
1 x Mounting Plate, 1 x Mounting Cell
1 x Isolation Kit
4. CROSS-DUCT EXCEL
Maximum cable length (m)
consumption
with 1.5mm
(W)
13
1 x Transmitter
2
conductors
(12ohms/km)
340
2 x Mounting Straps
1 x Receiver
60
Searchline Excel
Maximum cable length (m)
with 2.5mm
2
conductors
(7.6ohms/km)
540
Nuts, Bolts & Washers