APPENDIX A - HANDHELD INTERROGATOR
Gas Units
Effective Full Scale
Show Config
This option displays the configuration parameters the user can set in the same way as for the
Show Gas option. The configurable settings and values are shown in the following table:
Configuration Parameters Display Text
Protocol Address
Time to Block
Time to Fault
Max Response
Analogue Style
Inhibit Current
Block Current
Low Signal Current
Low Signal Level
Alarm Threshold
Report fault due to blockage RPRT Blocked Fault
Show Install
This option displays the installation configuration parameters in the same way as for the
Show Gas option. The configurable settings and values are shown below:
Installation Configuration
Parameters
System Type
Path Length
Gas Units
Gas Full Scale 0.1
Digital Address
Block Warn Time
Block Fault Time
Maximum T90
Analogue Mode
Inhibit mA
Blocked mA
Low Signal mA
Low Signal %
Alarm Threshold
Display Text
System Type
Path Length
116
LELm,
PPMm,
UEGm, or
VVm
%LEL (Cross-Duct only)
Min Value
Max Value
0
255
5s
600s
0s
600s
1s
60s
Alarm or Continuous
0mA
3mA
0mA
4mA
0mA
4mA
0%
90%
10%
100%
Enable or Disable
Description
Short Range
Medium Range
Long Range
Duct Mount
5m min.
0.5m min.
Searchline Excel
100000
0.05
Step Size
Default Values
1
0
5s
30
5s
120
1s
60
C
0.05mA
2.0
0.05mA
2.5
0.05mA
3.0
1%
33%
1%
20%
E
200m max.
1m step
5m max.
0.1m step