Honeywell AlarmNet IGSMHS Installation And Setup Manual page 31

Internet communication module
Table of Contents

Advertisement

PROMPTS
Direct Wire
Y/N
15
(N)_
Keypad Address
16
(28)_
17
Supervision
(UL Hi Line Sec)_
NOTE: The next prompt only appears if the Comm Path Choice is IP&GSM.
GSM 24Hr Tst
18
Y/N
(N)_
Old Alarm Time
19
10 Minutes_
4204/
ZONE
ENTRY
TRIG.
2-4204
Section 3: Programming the IGSMHS
OPTIONS
[Y], [N]
Enables Direct Wire Downloading over IP. This
applies only to the Vista-32FB and VISTA BP
and FBP series control panels with revision 3.x.
BP and FBP panels rev 4.x and higher support
Downloading via IP over ECP. If [N], skip to
Prompt 17: "Supervision."
[01-30]
Must be programmed if using Direct Wire
downloading. Enter the appropriate device
address.
NOTES:
1. This address must also be programmed as an
alpha keypad in the control panel or an AUI
(Advanced User Interface) type device, if a full
enhanced graphic interface to the system is
desired and the control panel supports it. DO
NOT connect an actual keypad (or any other
device) assigned to this address.
2. This address must be unique from the "Device
Address" entered in Prompt 14, and cannot
equal that device address plus 1 (one) if using
2-4204 mode.
 UL Hi
The AlarmNet network must hear at least one
supervisory message from the module during
Line Sec
this supervision period; otherwise, AlarmNet
 3 Min-
notifies the central station that a communica-
utes
 6 Min-
tion failure has occurred. (If the supervision
period is changed after registration, you must
utes
re-register the module.)
Press the [space] key to scroll through choices.
NOTE: When "UL Hi Line Sec" is selected, a
loss of communications is treated as an alarm
condition.
UL: Must be set to "UL Hi Line Sec" (200 sec).
[Y], [N]
If enabled a message is sent every 24 hrs over
GSM to verify proper operation. If it fails, a
Periodic Comm Test Failure message will be
sent over Ethernet.
UL: Must be set to "Y".
 10 Min
Sets how long an undeliverable alarm is retried
 15 Min
for delivery to the central station. If the
 30 Min
message is not validated, it is retried until the
 1 Hr
old alarm time is reached or the message is
 2 Hrs
validated.
 4 Hrs
Press the [space] key to scroll through choices.
 8 Hrs
 12 Hrs
UL: Must be set to 10 minutes.
 24 Hrs
DESCRIPTION
3-13

Advertisement

Table of Contents
loading

Table of Contents