Configure the Rack Server
Configure the Rack Server
To configure and check connectivity for a rach server, follow the steps in the
A for UCS Mini, on page 75
Reset Fabric Interconnects
To reset the fabric interconnects, follow theses steps:
Before you begin
After completion of examining the text log files, save the files in the designated location.
Procedure
Step 1
At the Fabric Interconnect B console, enter the following command:
Example:
Fabric-B# connect local
Fabric-B (local-mgt)# erase config
Step 2
At the warning prompt, enter
Step 3
Do not disconnect the fabric interconnect until it starts to reboot.
Step 4
After the fabric interconnect power cycles and initializes, disconnect the power cords.
Step 5
Repeat the preceding steps for Fabric Interconnect A.
Step 6
When the configurations on both fabric interconnects have been erased, reconnect the power cords.
Step 7
Verify that both fabric interconnects reboot and prompt you to Enter the configuration method.
Cleanup
To clean up after running diagnostics, follow these steps:
Procedure
Step 1
Power off all applicable PDUs in the rack.
Step 2
Disconnect the Digi Console and the Mgmt0 cables.
Cisco R42612 Rack and RP-Series Metered Input PDU Installation Guide
80
section through the "Event Logs" subsection.
Yes.
Integrating UCS Components in the Dynamic Rack
Configure Fabric Interconnect