Honeywell Gent Viglion EN54 Generic Commissioning Instructions page 98

For the fire alarm systems
Table of Contents

Advertisement

Generic Commissioning instructions
Message
A spurious FIRQ
at card x
A spurious IRQ
at card x
A spurious NMI
at card x
A spurious SWI2
at card x
A spurious SWI3
at card x
Access fault at
card x
ACIA Failed at
card x
Alarm Zone
Disabled /
Enabled at
card x
Alarms silenced
Alarms sounded
Alarms Verified
Allocation
:
memory Overflow
at card x number
y on loop z
Allocation :
Double Allocated
card x
number y on
loop z
Allocation : Hw
fault
card x
number y on
loop z
Allocation : Map
error card x
number y on
loop z
98
associated with..
meaning..
MCC / MCB (main
There is glitch on the MCC
control card/board)
hardware that appears on
the backplane / MCB.
MCC / MCB (main
There is glitch on the MCC
control card/board)
/ MCB hardware.
MCC / MCB (main
There is glitch on the MCC
control card/board)
/ MCB hardware.
MCC / MCB (main
There is glitch on the
control card/board)
MCC hardware.
MCC / MCB (main
There is glitch on the MCC
control card/board)
/ MCB hardware.
Any Card
Card cannot talk to the
MCC / MCB local
controller.
Network Card or
Communication chip
MCC / MCB
failure or the FABs and
SABs are corrupt.
Loop Processor
-
Card
MCC / MCB (main
Silence alarms button has
control card/board)
been pressed.
MCC / MCB (main
Sound alarms button has
control card/board)
been pressed.
MCC / MCB (main
Alarms verify or
control card/board)
acknowledge button has
been pressed.
Loop
Loop processor has run out
Processor
of memory during
Card
allocation / when starting a
loop.
Loop Processor
Two devices are given the
Card
same address. Loop breaker
(relay contacts) are fused
'micro welded' together
(closed) or there is a bad
connection.
Loop Processor
Loop breaker relay has not
Card
closed or serial line End-2
is faulty or relay is stuck
i.e. closed. The device may
not be correctly fitted.
Loop Processor
Loop wiring is incorrect, eg
Card
a sub loop may have been
wired on a spur.
..possible action
Clear and ignore single
occurrence.
Clear and ignore single
occurrence.
Clear and ignore single
occurrence.
Clear and ignore single
occurrence.
Clear and ignore single
occurrence.
Replace card if the fault
keeps reoccurring.
Could also be caused by
excessive network messages.
Investigate message passing.
Reset the card and replace if
it fault keeps reoccurring.
-
-
-
Software error or more likely
a faulty RAM chip.
The device may be faulty.
Check the device
connections.
Check and rewire if
necessary. This fault can also
be device failure.
4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.