Installation instructions
Checks
¨
Set the rotary switch SW2 to a required function.
¨
Ensure all DIP switches of SW1 are set to the Off
position before installing the IO card in the backplane
of Vigilon or 34000 system Control panel or Network
node.
¨
A 20 way ribbon cable connects between DKC
connector P4 and the IO card socket P2.
¨
One additional IO card can be fitted into the spare
socket on the backplane of the Vigilon/34000/3400
control panels and up to four into the backplane
sockets of the associated Network node.
When installing an additional IO card it is important to
set its DIP switches SW1 to the required baud rate and
node address and the rotary switch SW2 to the
required function before installing the card in a spare
socket of the backplane.
Setting switches SW1 and SW2
Off
SW1
new IO Card
Vigilon,
34000,
1 2 3
3400
3300 Mark 1
P3
1 2 3
32000 &
3300 Mark 2
P3
"
IMPORTANT:
The Vigilon and 34000 Control Panels make use of the DIP
switches on the DKC, located on the inner door. The
switches are used to set address and baud rate. For these
panels it is important that the DIP switches SW1 on the IO
card are ALL set in the UP or OFF position so that they
are ignored.
Gent by Honeywell reserves the right to revise this publication from time to time and make changes to the content hereof without
obligation to notify any person of such revisions of changes.
Hamilton Industrial Park, Waterside Road, Leicester LE5 1TN, UK
Telephone +44 (0) 116 246 2000
2
On
P2
SW2
Factory
set to 0
IC4
new IO Card - version 3+ (BS)
SW1 Switch settings
The switch positions shown here are applicable for the new IO
Card when installed as an additional IO card in the Vigilon or
34000 panel or node.
"
No dongle is required for the DIP switches to
work, when used as a second or additional IO card.
Baud Rate
1
2
3
|
Off Off Off 1200 baud
Off Off On 1800 baud
Off On Off 2400 baud
Off On On 3600 baud
On Off Off 4800 baud
On Off On 7200 baud
On On Off 9600 baud
On On On 19200 baud Off Off On On On
SW2 Switch settings
Rotary
Standard connections
switch
Port 0 (RS232) Mode
Pos.
0 or 8 3217 Half Duplex
1 or 9 Slave I/O
2 or A Remote Printer (as
VIG-IOC-PRT-V3+)
3 or B Universal Full-Duplex (as
VIG-IOC-UFD-V3+)
4 or C Ascom Pager (as
VIG-IOC-ASCOM-V3+)
5 or D Domain Bridge Full-Duplex
6 or E Universal Half-Duplex (as
VIG-IOC-UNI-V3+)
7 or F -
Factory settings
WEEE Directive:
At the end of their useful life, the packaging,
product and batteries should be
disposed of via a suitable recycling centre.
Do not dispose of with your normal household waste.
Do not burn.
new IO Card V3+ (BS) 4188-797 issue 2_7/05
Node Address
5|
6
7
8
|
4
Off Off Off Off Off
Off Off Off Off On
1
Off Off Off On Off
2
Off Off Off On On
3
Off Off On Off Off
4
Off Off On Off On
5
Off Off On On Off
6
7
|
On On On On On up
to
31
Port 1
(RS485
mode)
Switch
position from
0 to 7 sets this
port for
Repeat panel
at 1200 baud.
Switch
position from
8 to F sets
this port for
other
applications at
9600 baud.
Website: www.gent.co.uk