Honeywell Gent Viglion EN54 Generic Commissioning Instructions page 186

For the fire alarm systems
Table of Contents

Advertisement

Initial alignment
Beam sensor alignment
Initial alignment
Vigilon Sys tem Com mis sioning
NOTE: Before aligning the sensor heads check to ensure all bracket and
base fixing screws are securely fitted. After alignment ensure the pivot
pins and adjusters are secure.
a)
Using the adjuster on the bracket, roughly align one head to face the
other head. To do this:
• slacken the locknuts to unscrew the Y- adjusters
• to make a large adjustment remove the centre pin of the Y pivot
• align the head in the Y-axis to face the opposite head
• secure the centre pin into the appropriate Y-pivot, to enable
adjustment
• turn the adjusters to meet the centre pin and lock the axis adjusted
using the lock nuts.
• repeat procedure for the X-adjusters
• repeat the whole procedure for the opposite head.
VIG-BEAM Beam sensor
Figure 6-2 Beam sensor with bracket assembly
cdm44