Honeywell Gent Viglion EN54 Generic Commissioning Instructions page 100

For the fire alarm systems
Table of Contents

Advertisement

Generic Commissioning instructions
Message
Call point glass
is broken
number x loop y
Call point on
interface unit
operated/
restored
Call point open
cct number x on
loop y
Call point
operated/restore
d number x
loop y
Call point short
cct number x
loop y
Card found/lost
at card x
Card n recovered
/Card n backed
up
Chamber Removed
/Replaced number
x on loop y
Charger Fault
Charger Fault
number x on
loop y
Charger Restored
Charger Restored
number x on
loop y
Chk=4.874 NVMC
41874 Flag=0
NVM is write
protected at
Card x
100
associated with..
meaning..
Device
Call point has been
operated when the device is
disabled.
Device
Mains powered interface
input has been triggered by
conventional MCP. Value
of input is equal to or less
than 6V.
Device
Monitored base does not
see end-of-line unit. There
is a bad connection to
MCP.
Device
Break glass has been
broken or operated with a
test key.
Device
Call point contacts are
short circuit.
Any Card
The card has been
found/lost. If lost then it is
locked out.
Memory (NVM) -
Data recovered to a card
Backplane
from the NVM. A card data
has been backed up to the
NVM.
Device
Device chamber has been
removed.
Panel
Charger circuit has failed.
Power Supply Unit
(PSU)
EN54 System device
Charger circuit has failed.
power supply
(Repeat, Mimic or
mains powered
interface)
Panel power supply
Charger circuit is working
again.
EN54 System device
Charger circuit is working
power supply
again.
(Repeat, Mimic or
mains powered
interface).
Memory (NVM) -
The memory is read only.
Backplane
..possible action
Replace the glass, if
necessary.
-
Check the internal wiring,
there may be a loose
connection.
Replace the break glass to
restore the call point or
remove the test key,
whichever is applicable.
Check the call point contacts
and circuit internally.
There may be a hardware
fault on card or Bckplane.
Investigate and rectify.
-
Replacing the chamber will
cause a replaced indication.
Replace the PSU.
Replace the board (having the
power supply) on the loop
device.
-
-
Disable the write protect
using the [set up] menu.
4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.