How To Configure The 'U' Buttons And Cb254 Led; How To Fit The Outer Door - Honeywell Gent Viglion EN54 Generic Commissioning Instructions

For the fire alarm systems
Table of Contents

Advertisement

System configuration
All devices are assigned to sector 1
All devices are assigned to zone 1
How to configure the 'U' buttons and
CB254 LED
U1 to U4 buttons
The U1, U2, U3 and U4 buttons are active at access level 2, that
is the buttons are accessible by opening the panel door.
)
+
0
-
:
P
;
;
,
.
Fire
Part of the Keyboard
On operating a 'U' button the panel will trigger command build.
¨
U1 button will trigger command build number 251
¨
U2 button will trigger command build number 252
¨
U3 button will trigger command build number 253
¨
U4 button will trigger command build number 254
During commissioning the required command build action must
be configured.
Example 1
This example shows how to configure the U1 button such that
pressing it will start the master alarm sounders and pressing
Silence alarm button will stop the sounders.
The following procedures assume a password entry is not
required.
Press Menu On/Off button and select [SetUp], momentarily
press <etc> to select [SetUp] -> [Build] and type in the
command build number 251, select [Action] -> [Start MA] ->
[Enter] -> [Non Reversbl] -> [Enter]. The U1 button is now
configured to start the master alarm sounders.
Example 2
This example shows how to configure the U1 button such that it
operates an output of an interface unit and releasing the U1
button it returns the output to normal condition.
The following procedures assume a password entry is not
required.
Press Menu On/Off button and select [SetUp], momentarily
press <etc> to select [SetUp] -> [Build] and type in the
command build number 251, select [Action] -> [Usercode] and
momentarily press <etc> to select -> [Digital] and type in the
interface output channel number, select [On] and type in the
interface device number, select [Loop] and type in the loop
number -> [Enter], now select [Reversbl] and then [Enter]. The
U1 button is now configured to switch on the digital output on an
interface unit and on releasing it will switch off the output.
4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.
Insert
U1
U2
Delete
U3
Enter
U4
Space
Vigilon (EN & BS) Compact (VA) panels
CB253 & CB254 LEDs
The switching of the LED CB253 or CB254 result from a trigger
of command build 253 or 254. The switching action must be
configured during commissioning.
Indicators
Fire
Verify
Sounder
CB253
CB254
Power
This example shows how to configure the panel such that by
activating an interface input (can be a push button switch), it will
cause the panel LED - CB254 and Master alarms to switch On. If
the interface input is released, then the panel LED-CB254 and
Master alarms will switch Off.
The following procedures assume a password entry is not
required.
Firstly set up command build 254 to be triggered by an interface:
Press Menu On/Off button and select [SetUp] , momentarily
press <etc> to select [SetUp] and [Build], type in the command
build number 254, select [Trigger] and [IO line], type in the
interface input channel number, select [Device], type in the
interface device number, select [Loop], type in the loop number
and then select [Enter]. The command build 254 is now
configured to be triggered by the interface input.
Now to create a command build label:
Press Menu On/Off button and select [SetUp], momentarily
press <etc> to select [SetUp] and [Build], type in the command
build number 254, select [Label] and type in a label of up to 40
character in length, select [Display] to display the label on the
panel when the command build 254 is triggered.
Now to set up the action of command build 254:
Press Menu On/Off button and select [SetUp], momentarily
press <etc> to select [SetUp] and [Build], type in the command
build number 254, select [Action] and [Start MA], [Enter],
[Reversbl] and [Enter].

How to fit the outer door

To close the outer door you will first need to close the inner door
and secure it to the backbox using the two fasteners located on
the right edge of the inner door.
Fit the Outer door to the enclosure by hooking it onto the side
hinge pins. The outer door may be secured to the backbox using
the key lock.