Honeywell Gent Viglion EN54 Generic Commissioning Instructions page 108

For the fire alarm systems
Table of Contents

Advertisement

Generic Commissioning instructions
Message
No periodic
interrupts at
card x
No response
number x loop y
No room on NVM
card
Node double
allocated at
card x
Node found at
Card x
Node
lost/restored at
Card x
Not enough RAM
at card x
Nothing found at
Card x
NVM initialised
NVM is not write
protected
NVM is read only
Panel in/out of
commissioning
mode
Panel Label Set
up
Panel powerup
Pattern
number x on loop
y channel x
Pointer
corrupted at
Card x
108
associated with..
meaning..
Any Card
Problem with software, the
watchdog will operate the
MCC / MCB (main control
card/board).
Loop Processor
There is no communication
Card
with repeat or mimic panel
software.
Backplane (with
User attempts to backup or
memory)
save to an NVM that does
not have enough free space
Network Card
Two network cards have
same address.
Network Card
Another panel on the
network acknowledged.
Network Card
There have been 15
missing replies from
another panel.
Any Card
Not enough memory.
Loop Processor
No devices found on End 1
Card
or End 2.
Memory (NVM)-
Memory available verified.
Backplane
Memory (NVM)-
Read and write is possible
Backplane
to the memory card.
Backplane (with
User attempts to write to a
memory)
hardware write protected
NVM card
MCC / MCB (main
Commissioning mode
control card/board)
switched ON/OFF.
MCC / MCB (main
Panel label has been set
control card/board)
from the menu.
MCC / MCB (main
Software reset of system or
control card/board)
there has been a manual
reset of card 0.
Loop Processor
Sensor has detected an
Card
interesting event eg
fire/fault.
Any Card
Software error.
..possible action
Software error will activate a
system reset.
Ignore single occurrence.
Record event in log book.
Power-up the repeat or mimic
panel.
If there is no memory left
then the card 14 located on
Backplane needs to be
initialised
Keep address unique.
-
Check the wiring or check
and reset the panel Network
card to restore.
Reset the card and ignore
single occurrence. If
necessary replace the card or
add RAM, where applicable.
Check wiring of loop circuit.
-
Enable protect if required
using the [set up] menu.
Remove the hardware write
protect before writing
To manually switch
commissioning mode use the
[Test/Eng] menu.
-
If an automatic reset has
occurred than check for
system errors.
-
Software errors will activate
a system reset.
Ignore single occurrence.
Record the event in log
book.
4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.