Honeywell Gent Viglion EN54 Generic Commissioning Instructions page 149

For the fire alarm systems
Table of Contents

Advertisement

Installation instructions
Conversion kit
(2534-196)
This kit may be required when installing a replacement PSU in
a Vigilon panel.
"
If upgrading to new earthing arrangement
the EMC cover part number 4094-290.01 will be required
and is available free of charge upon request from GENT
Sales.
&
Before working on the panel you must
first power down the mains and battery supply to
the panel.
Kit
This kit must be used to correctly wire the replacement PSU
No.

Back box spade connector to mains
input filter earth. Yellow/Green wire
Back box spade connector to PSU
earth. Yellow/Green wire
ƒ
Mains filter to PSU live (brown) and
neutral (blue) wire loom
Spade connector
Primary earth label
Nut
ˆ
Shake proof washer
"
The parts in the kits are used according to
the wiring arrangements.
Parts used
Parts used when converting the old earthing arrangement to
the new earthing arrangement:
ƒ„†‡ˆ
Items required:
Parts used when converting the new earthing arrangement to
the old earthing arrangement:
‚ƒ…†‡ˆ
Items required:
Conversion kit 4188-823 issue 1_05/06
for PSU wiring in Vigilon panel
Qty
1
1
1
1
Cable tie
1
1
1
3
Wiring arrangements
Converting from the old earthing arrangement
Wiring arrangement
before replacing the PSU
N
E
L
PCE
Mains
Filter
N
L
N
TE
E
L
PCB
PSU Chassis
PSU with old
earthing arrangement
Converting from the new earthing arrangement
Wiring arrangement
before replacing the PSU
N
E
L
PCE
Mains
Filter
N
L
N
TE
L
PCB
PSU Chassis
PSU with New
earthing arrangement
TE - Transformer Earth
PCE - PSU Chassis Earth
by Honeywell
Wiring arrangement
after replacing the PSU
N
E
L
Mains
Filter
PCE
N
L
N
TE
L
PCB
PSU Chassis
PSU with new
earthing arrangement
Wiring arrangement
after replacing the PSU
N
E
L
Mains
PCE
Filter
N
L
N
TE
E
L
PCB
PSU Chassis
PSU with old
earthing arrangement
1