13.4 Overview parameter settings (factory default settings)

Parameter
Sensor Tag
Sensor Location Tag
Qv Max 1
Unit Volumeflow Qv
Unit Vol. Totalizer
Pulses per Unit
Pulse Width
Damping
Operating mode digital output 41 / 42
Operating mode digital output 51 / 52
Curr.Out 31 / 32
Curr.Out at Alarm
Current at flow > 103 % (I=20,5 mA)
Low flow cut-off
Empty conduit detector
Possible parameter settings
Alphanumeric, max. 20 characters
Alphanumeric, max. 20 characters
Depending on nominal diameter of the flowmeter
sensor.
l/s; l/min; l/h; ml/s; ml/min; m3/s; m3/min; m3/h;
m3/d; hl/h; g/s; g/min; g/h; kg/s; kg/min; kg/h;
kg/d; t/min; t/h; t/d
m3; l; ml; hl; g; kg; t
1 ... 10000
0,1 ... 2000 ms
0,02 ... 60 s
Off, binary output, pulse output, frequency
output
Off, binary output, pulse output (follows digital
output 41 / 42, 90° or 180° phase shift)
4-20mA FWD/REV, 4-20mA FWD, 4-12-20 mA
High Alarm 21 ... 23 mA oder Low Alarm
3.5 ... 3.6 mA
Off (Current output remains at 20.5 mA), High
Alarm, Low Alarm.
0 ... 10 %
On / Off
ProcessMaster FEP610, HygienicMaster FEH610 | OI/FEP610/FEH610-EN Rev. B 93
Factory default settings
None
None
Set to Q
DN according to chapter "Measuring
max
range table" on page 37.
l/min
Liter (l)
1
100 ms
1
Digital output 41 / 42 as pulse output for forward
flow and reverse flow.
Digital output 51 / 52 as binary output for flow
direction.
4-20mA FWD/REV
High Alarm, 21.8 mA
Off
1 %
Off