7.5.2

Menu: Easy Setup

Menu / parameter
Easy Setup
Language
Unit Volumeflow Qv
Qv Max 1
Unit Vol. Totalizer
Pulses per Unit
Pulse Width
Damping
Dig.Out 41 / 42 Mode
Upper Frequency
Curr.Out at Alarm
Low Alarm
High Alarm
System Zero
50 OI/FEP610/FEH610-EN Rev. B | ProcessMaster FEP610, HygienicMaster FEH610
Description
Selection of menu language (German, English, French, Spanish, Italian, Chinese, Portuguese).
Selection of the unit for the volume flow (e.g. for the parameters QvMax / QvMaxDN and for the corresponding
process value).
Default setting: l/min
See Table "Table 1: Units for the volume flow" on page 49.
Setting of the upper measuring range value 1 (Measuring range = 0 ... Qv Max 1) for the volume flow for forward
flow and reverse flow.
Default setting: 1 x Q
DN
max
Selection of the unit for the volume totalizers and the pulse outputs.
Default setting: l (liter)
See Table "Available units" on page 49.
Set pulses per volume or per mass flow unit, and the pulse width for the digital output operating mode "Pulse". The
pulse factor and pulse width are interdependent and are calculated dynamically (Pulses per unit: 1 ... 10000/s,
Pulse width: 0.1 ... 2000 mS).
Only available if a digital output has been configured as a pulse output, and the volume flow or mass flow has been
selected as the process variable to be output.
Select the damping.
The value (0.02 ... 60 s) set here relates to 1 Τ (Tau). The value refers to the response time for a step flowrate
change. It affects the instantaneous value in the display and at the current output.
Default setting: 1 second
Selection of the operating mode for digital output 41 / 42.
— Off: Digital output 41 / 42 deactivated.
— Logic: Digital output 41 / 42 as a binary output (e.g. as an alarm output).
— Pulse: Digital output 41 / 42 as a pulse output. In pulse mode, pulses are output per unit (e.g. 1 pulse per m3).
— Frequency: Digital output 41 / 42 as a frequency output. In frequency mode, a frequency is issued that is
proportional to the flow rate. The maximum frequency can be configured in accordance with the upper range
value.
Default setting: Pulse
Sets the upper range value frequency for the digital output operating mode "Frequency". The entered value
(0 ... 10500 Hz) corresponds to 100 % flow.
Only available if a digital output has been configured as a frequency output, and the volume flow or mass flow has
been selected as the process variable to be output.
Selection of status of the current output in error condition.
The output "Low Alarm" or "High Alarm" current is set in the subsequent menu.
Sets the current (3.5 ... 3.6 mA) for Low Alarm.
Sets the current (21 ... 22.6 mA) for High Alarm.
Starts the automatic zero point adjustment using
NOTE
Prior to starting the zero point adjustment, make sure that:
— There is no flow through the sensor (close valves, shut-off devices etc.).
— The sensor must be filled completely with measuring medium for measurement.
. Automatic zero point adjustment takes approx. 60 seconds.