5.5.6

Electrical data for inputs and outputs

Power supply L / N, 1+ / 2-
AC power supply
Terminals
L / N
Operating voltage
100 ... 240 V AC (-15 % / +10 %), 47 ... 64 Hz
Power consumption
< 20 VA
Inrush current
8.8 A
DC voltage supply
Terminals
1+ / 2-
Operating voltage
24 ... 48V DC (-10 % / +10 %)
Ripple
< 5 %
Power consumption
< 10 W
Inrush current
5.6 A
Current output 31 / 32
Can be configured for outputting mass flow, volume flow.
I
+31
-32
Fig. 37: Connection example active current output 31 / 32
(I = internal, E = external, R
Current output
Active
Terminals
31 / 32
Output signal
4 ... 20 mA
Load R
0 Ω ≤ RB ≤ 650 Ω
B
Change from two to one column
26 OI/FEP610/FEH610-EN Rev. B | ProcessMaster FEP610, HygienicMaster FEH610
E
R
B
4 ... 20 mA
G12037
= load)
B
Digital output 41 / 42, 51 / 52
Can be configured as pulse, frequency or binary output.
A
I
41
51
42/52
B
I
41
51
42/52
Fig. 38: Connection example (I = internal, E = external, R
A Passive digital output 41 / 42, 51 / 52 as pulse or frequency output
B Passive digital output 51 / 52 as binary output
NOTE
— Terminals 42 / 52 have the same ground potential.
Digital outputs 41 / 42 and 51 / 52 are not electrically
isolated from each other.
— If you are using a mechanical counter, we recommend
setting a pulse width of ≥ 30 ms and a maximum
frequency of fmax ≤ 3 kHz.
Pulse / frequency output (passive)
Terminals
41 / 42, 51 / 52
U
30 V DC
max
I
25 mA
max
f
10.5 kHz
max
Pulse width
0.1 ... 2000 ms
Binary output (passive)
Terminals
41 / 42, 51 / 52
U
30 V DC
max
I
25 mA
max
Switching function
Can be configured using software as:
System alarm, empty pipe alarm, max. / min.
alarm, flow direction signaling, others
16 ... 30 V
-
+
E
R
B
R
B
E
R
B
0 V
24 V DC
B
U
R
CE
B
I
CE
U
R
CE
B
I
CE
G11597-01
= load)