Error Messages On The Lcd Display; Switching To The Configuration Level (Parameterization) - ABB ProcessMaster FEP611 Operating Instructions Manual

Table of Contents

Advertisement

7.3.3

Error messages on the LCD display

In the event of an error, a message consisting of a symbol and
text (e.g. Electronics) appears at the bottom of the process
screen.
The text displayed provides information about the area in
which the error has occurred.
Process display
Electronics
The error messages are divided into four groups in
accordance with the NAMUR classification scheme. The group
assignment can only be changed using a DTM or EDD:
Symbol
Description
Error / failure
Function check
Outside of the specification
Maintenance required
The error messages are also divided into the following areas:
Range
Description
Operation
Error / alarm due to the current operating
conditions.
Sensor
Error / alarm of the flowmeter sensor.
Electronics
Error / alarm of the electronics.
Configuration
Error / alarm due to device configuration.
NOTE
For a detailed description of errors and troubleshooting
instructions, please see chapter "
Diagnosis / error messages" on page 64.
7.3.4
Switching to the configuration level
(parameterization)
The device parameters can be displayed and changed on the
configuration level.
Process display
1. Use
to switch to the configuration level.
Access Level
Read Only
Standard
Advanced
Back
2. Select the desired level of access using
3. Confirm the selection with
NOTE
There are three levels of access. A password can be defined
for level "Standard".
There is no factory default password.
Access Level
Description
Read Only
All parameters are locked. Parameters are read
only and cannot be modified.
Standard
All the parameters can be altered.
Service
Only Customer Service has access to the Service
menu.
ProcessMaster FEP610, HygienicMaster FEH610 | OI/FEP610/FEH610-EN Rev. B 41
Select
/
.
.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents