Fii-Rtd; Rtd, 4-Wire Connection (Board Id = 2); Rtd, 3-Wire Connection (Board Id = 3) - Honeywell Enraf SmartRadar FlexLine Installation Manual

Table of Contents

Advertisement

Installation

4.11.4.3 FII-RTD

Cable specifications
Type
Maximum length

4.11.4.3.1 RTD, 4-Wire Connection (Board ID = 2)

Label
30. RTD1_S-
31. RTD1_com
32. RTD1_pos
33. RTD1_S+
34. RTD2_S-
35. RTD2_com
36. RTD2_pos
37. RTD2_S+

4.11.4.3.2 RTD, 3-Wire Connection (Board ID = 3)

Label
30. RTD1_S-
31. RTD1_com
32. RTD1_pos
34. RTD2_S-
35. RTD2_com
36. RTD2_pos
Part No.: 4417.760_Rev06
Shielded. R
max
150 meter
Connections diagram
R
c1
RTD1
R
c2
RTD2
Connections diagram
R
c1
RTD1
R
c2
RTD2
= 100 Ω / line
Parameters
[Ex ia] IIB/IIC
U
= 8.61 V
o
I
= 58 mA
o
P
= 0.13 W
o
= 1.0 μF
C
o
L
= 10.5 mH
o
Parameters
[Ex ia] IIB/IIC
U
= 8.61 V
o
I
= 58 mA
o
P
= 0.13 W
o
= 1.0 μF
C
o
L
= 10.5 mH
o
SmartRadar FlexLine
Installation Guide
39

Advertisement

Table of Contents
loading

Table of Contents