Compound Glands; Conduits - Honeywell Enraf SmartRadar FlexLine Installation Manual

Table of Contents

Advertisement

Installation
CAUTION!
Improper installation of cable glands, conduits, or
stopping plugs will invalidate the Ex approval of the
SmartRadar.
NOTE:
Only for use in ATEX and IEC Ex approved installations.

4.10.1 Compound Glands

 Use explosion proof (Ex-d) compound glands with an appro-
priate IP value.
NOTE:
Install the compound glands according to the instructions
provided by the manufacturer.

4.10.2 Conduits

 Use explosion proof (Ex-d) conduits with an appropriate IP
value. See the type plate on the device.
WARNING!
If the SmartRadar is installed in a hazardous area:
• Metal conduits must be used, size 3/4".
• Stopper boxes must be installed within 45 cm (18") of
the device to seal the cabling in the conduit.
NOTE:
Install the conduits according to the instructions provided
by the manufacturer.
Part No.: 4417.760_Rev06
SmartRadar FlexLine
Installation Guide
27