Cisco GS7000 Installation And Operation Manual page 38

Gainmaker node seg2way status monitor/local control module
Table of Contents

Advertisement

Chapter 3 Configuration
Result: The handheld terminal attempts to identify the device type of the node.
If recognized, terminal application "Node_GS7K.app", software number 538888,
is loaded into the handheld terminal's memory and the LCM/node configuration
menu items are available. If the handheld terminal's screen does not illuminate,
make sure that its plug is fully inserted into the local control port on the module.
Note: If the handheld terminal cannot identify the device type, or cannot find its
associated terminal application, the LCM/node configuration menu items will
not load. Refer to the handheld programming terminal's download kit user
documentation.
2
Select menu item 1 - RX & TX Config and enter its sub-menu.
a
Set receivers RX1 through RX4 and transmitters TX1 through TX4 as Present
or Absent in the node.
3
Select menu item 2 - PS Config and enter its sub-menu.
a
Set AC inputs AC1and AC2, plus power supply modules PS1 and PS2 as
Present or Absent in the node.
4
Select menu item 3 - RX Thresholds and enter its sub-menu.
a
Set the minimum and maximum power thresholds for receivers RX1 through
RX4.
Note: This sets the switching levels for the two AB switches. The defaults
are 0.5 mW minimum and 2.0 mW maximum.
5
Select menu item 4 - TX Thresholds and enter its sub-menu.
24
4022871 Rev C