Table 2-41 Range/Limit Tab Configuration Parameters - Honeywell UMC800 Reference Manual

Control builder function block
Hide thumbs Also See for UMC800:
Table of Contents

Advertisement

Function Blocks
2.50 PID Function Block,
Configuration Parameters, continued
RANGE/LIMIT TAB, continued
Properties Group
Parameter
Ranging
Display
Range (EU)
Limiting
SP Rate Up
146
continued

Table 2-41 Range/Limit Tab Configuration Parameters

Index#
4
PV High
range
PV Low
5
Range
N/A
Decimal
Places
N/A
Units
N/A
DEV Bar
SP High
11
Limit
12
SP Low
limit
14
Out High
Limit
Out Low
15
limit
35
SP Rate
Down
36
Function Block Reference Guide
Parameter Description
PV High Range Value
PV Low Range Value
Number of digits to display after
decimal point.
Text to display for EU
Deviation Bar Range on the
Operator Interface
Setpoint High Limit Value -
prevents the local and remote
setpoints from going above the
value set here.
Setpoint Low Limit Value -
prevents the local and remote
setpoints from going below the
value set here.
Output High Limit Value - is the
highest value of output beyond
which you do not want the
automatic output to exceed
Output Low Limit Value - is the
lowest value of output beyond
which you do not want the
automatic output to exceed
Setpoint Rate Down value -
when making a setpoint change,
this is the rate at which setpoint
will change from the original
setpoint down to the new one.
Setpoint Rate Up value - when
making a setpoint change, this is
the rate at which setpoint will
change from the original setpoint
up to the new one.
Value or Selection
-99999 to 99999
-99999 to 99999
0 to 5
4 characters
-99999 to 99999
-99999 to 99999
-99999 to 99999
-5 to 105%
-5 to 105%
0(off) to 9999
(eu/min)
0(off) to 9999
(eu/min)
3/99