Table 2-19 Dewpoint Function Block Parameters - Honeywell UMC800 Reference Manual

Control builder function block
Hide thumbs Also See for UMC800:
Table of Contents

Advertisement

Function Blocks
2.18 DEWP Function Block,
Properties Group
Parameter
Furnace
Properties
Temperature
CO Properties
Carbon Probe
O2 Probe
Manufacturer
Manufacturer
64
continued

Table 2-19 Dewpoint Function Block Parameters

Index#
Furnace
2
Factor
3
5
Low
Limit
4
7
Percent
Hydrogen
%CO
0
1
N/A
Function Block Reference Guide
Parameter Description
Allows you to adjust the %
Carbon as measured by the
controller to agree with the
results of actual shim stock
tests. This adjustment may
be needed to correct for
specific furnace
characteristics such as
atmosphere differences,
probe location, and furnace
leaks.
Activates anti-sooting feature
that limits the working
setpoint of the carbon control
loop to a value that prevents
sooting in the furnace.
Holds controller output to 0%
until limit is exceeded.
Probe temperature units for
display.
Percent Hydrogen
Allows you to adjust %
Carbon measurement to
compensate for variations in
the amount of CO in the
carrier gas.
Function block will use the
actual %Carbon Monoxide
that is defined through an
analog input.
Select from Drop Down List
of Manufacturers.
Value or Selection
-0.5 to +0.5%C
Click on block to select
SP HLIM is used for anti-
soot.
0 to 2500 degrees F
(1400° recommended)
Unit should match C/F
selection
Click on radio button
to select
1 to 100
default = 40
2.0 to 35.0
default = 20
Click on block to select
Advanced
Atmosphere Control
Corp.
Furnace Control
Corp.
Marathon Monitors
Super Systems Inc.
3/99