HIGH teMPeRAtURe LIMIt
The high temperature limit has been configured at the factory and
should not require any adjustments. The procedure for changing the
limit or alarm setpoint and a configuration record are given below.
Detailed information is given in the vendor literature supplied with
the control panel.
Changing the limit or alarm setpoint
1 Hold the SETUP key and press the ▲ key. The lower display will
show SLCT and the upper display will read OPTR.
2 Release the SETUP key and press the ▲ key until the upper
display reads SETP then press SETUP again to display the current
limit setpoint.
3 Use the ▲ or ▼ keys to change the setpoint.
4 Press SETUP to advance to PhA1 and again use the ▲ or ▼ keys
to change the alarm setpoint if desired.
5 Hold SETUP and press the ▲ key then release the SETUP key
and press the ▲ key until the upper display again reads OPTR;
then press SETUP to return to the operating (normal) display.
ConFIGURAtIon ReCoRD sHeet
➔ SLCT = CONF
➔ ULOC = 20
Lower Display
Factory
(Function)
Configuration
INPT
RUL
RLL
OFFS
CTRL
SPUL
SPLL
ALA1
PHA1
AHY1
ALA2
PLA2
AHY2
USE2
USE3
DISP
CLOC
AHY2
AHY2
1 After completing Configuration, simultaneously press the ▲ and
SETUP keys. ConF will appear in the Upper Display.
2 Press the ▲ arrow key until the Upper Display reads SEtP then
press SETUP. ULoc will appear in the Lower Display.
3 Press the ▲ arrow until Upper Display reads 10.
4 Press SETUP to enter the set point mode.
Final
setting
J.F
999.9
-199.9
0.0
HI
999.9
-199.9
P_HI
380.0
0.1
PL_O
-199.9
0.1
A1_d
A2_d
ENAB
20
0.1
0.1
5 Set the limit set point at 400 F and PhA1 at 380 F. All other settings
remain at their factory defaults.
Lower Display
(Function)
Configuration
SP
HYSt
FiLt
PhA1
AHY1
PLA2
AHY2
SLoc
8
Factory
Final
setting
400.0
0.1
2
380.0
0.1
-199.9
0.1
10