2.25 FSYS Function Block

Description
The Fast Logic Status Block (FSYS) is a function block and is part of the Fast Logic category. It provides
read access to controller status values including those related to the Fast Logic execution cycle. The output
may be connected to function block inputs. The outputs may also be connected to signal tags for operator
interface monitoring. The FSYS System Monitoring block is assigned block number 250. It looks like this
graphically on the Control Builder:
Table 2-24 describes the outputs for the Fast Logic system status block.

Table 2-24 Fast Logic System Status Block Outputs

Output
NEWSTART
Newstart is ON for one full scan cycle of Fast Logic control block execution,
following a cold start of the controller. For example: starting after a change
from program to run.
RESTART
Restart is ON for one full scan cycle of Fast Logic control block execution,
following the warm start of the controller.
ALM ACTIV
Alarm Active is ON if any operator panel alarm is ON.
ALMUNACK
Alarm unacknowledge is ON if any operator panel's alarm is unacknowledged.
HWOK
Hardware OK is ON if there are no faults.
LOWBTRY
Low Battery is ON if the battery is low, Off when battery is good.
HI TEMP
High CJ Temperature is ON if the CJ temperature is high.
COMFAIL
Communications Failure is ON if there is a failure to the operator interface.
BAD BLOCK
Bad Block is ON when one or more blocks are not operating properly.
OFF LINE
Off Line is ON when the controller mode switch is in the Off Line mode.
3/99
Description
Function Block Reference Guide
Function Blocks
79