Figure 11: Connection Using Hub/Switch/Repeater - GE RX3i User Manual

Pacsystems
Hide thumbs Also See for RX3i:
Table of Contents

Advertisement

Chapter 3. Installation and Start-up: Rack-based and RX7i Embedded Interface
10Base-T/100Base Tx Port Pinouts
Note:
Pin assignments are provided for troubleshooting purposes only. 10Base-T/100Base-Tx
cables are readily available from commercial distributors. We recommend purchasing
rather than making 10Base-T/100Base-Tx cables.
Connection Using a Hub/Switch/Repeater
Connection of the Ethernet Interface to a 10Base-T or 100Base-Tx network is shown below.
To Other Network
Devices
Note:
Care must be taken with the use of active network control devices, such as managed
switches. If a device inserts excessive latency, especially in regards to the ARP protocol,
produced EGD exchanges may generate PLC Fault Table entries indicating the loss of a
consumer when the PLC transitions from STOP to RUN. EGD data will be successfully
transferred after an initial delay.
28
PACSystems* RX7i & RX3i TCP/IP Ethernet Communications User Manual
Pin Number
Signal
4
1
TD+
2
TD–
3
RD+
4
NC
5
NC
6
RD–
7
NC
8
NC
Hub/Switch/Repeater

Figure 11: Connection Using Hub/Switch/Repeater

Description
Transmit Data +
Transmit Data –
Receive Data +
No connection
No connection
Receive Data –
No connection
No connection
10/100
10/100
Ethernet
Interface
10BaseT/100Base Tx
Twisted Pair Cable
GFK-2224Q

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rx7i

Table of Contents