GE PACSystems RX3i IC695ACC403 Quick Start Manual
GE PACSystems RX3i IC695ACC403 Quick Start Manual

GE PACSystems RX3i IC695ACC403 Quick Start Manual

Rackless energy pack

Advertisement

GE
Automation & Controls
Programmable Control Products
PACSystems* RX3i
Rackless Energy Pack
IC695ACC403
Quick Start Guide
GFK-3000A
July 2018
For Public Disclosure

Advertisement

Table of Contents
loading

Summary of Contents for GE PACSystems RX3i IC695ACC403

  • Page 1 Automation & Controls Programmable Control Products PACSystems* RX3i Rackless Energy Pack IC695ACC403 Quick Start Guide GFK-3000A July 2018 For Public Disclosure...
  • Page 2: Table Of Contents

    Contents Overview ................1 Hardware Installation ........... 2 Mounting the Energy Pack on a DIN Rail .. 2 Panel-Mounting the Energy Pack ....3 Cable Connections ............4 Connect Input Power to Energy Pack ..5 Connecting the Energy Pack to the Controller ................
  • Page 3: Overview

    Overview An Energy Pack is used in conjunction with a Controller to preserve user memory in the Controller during power fluctuations or outages. If system power is lost, the Energy Pack maintains power long enough for a Controller to write its user memory contents to non-volatile memory.
  • Page 4: Hardware Installation

    Ordering Information Energy Pack. Includes base, IC695ACC403 CapPack module and Energy Pack to Controller cable. IC695ACC413 Replacement CapPack module. IC695CBL003 Replacement 0.6m (24”) Energy Pack to Controller cable. Hardware Installation The Energy Pack can be mounted on a standard EN50022 DIN rail or an equipment panel.
  • Page 5: Panel-Mounting The Energy Pack

    Figure 2: Snap Mount to DIN Rail Panel-Mounting the Energy Pack Recommended fasteners: Four M4-0.7 machine screws with minimum length of 25mm (or 8-32, 1” min. length) and nuts. CAUTION Over tightening the mounting screws could crack the plastic housing. July 2018 GFK-3000A...
  • Page 6: Cable Connections

    3 Cable Connections Figure 3: Input Power and Output Power /Control Connections GFK-3000A IC695ACC403 Quick Start Guide...
  • Page 7: Connect Input Power To Energy Pack

    3.1 Connect Input Power to Energy Pack IMPORTANT Before connecting input power, see complete installation instructions in the PACSystems Controllers: Battery and Energy Pack Manual, GFK-2741E or later. You will need: ▪ A 24Vdc, 72W SELV power supply A power cord with 18 AWG (0.82mm ) copper wires ▪...
  • Page 8: Connecting The Energy Pack To The Controller

    Figure 4: Energy Pack Input Power Mating Connector (bottom view) Insert the plug into the Energy Pack’s Input Power connector and securely tighten the attaching screws. Connecting the Energy Pack to the Controller With power to the system turned off, use the supplied cable (IC695CBL003) to connect the output of the Energy Pack (green connector) to the 24Vdc input on the Controller (3-pin green...
  • Page 9: Grounding

    Grounding Proper grounding of this device is essential. All ground wires must be as short as possible and terminated at the same grounding point. Figure 5: Frame Ground Connection July 2018 GFK-3000A...
  • Page 10: Initial Power-Up

    5 Initial Power-up When 24Vdc power is first applied to the Energy Pack, the power-up process goes through the following steps: The IN LED turns on green. The Energy Pack performs a self-diagnostic test. If this test passes, output power to the Controller is turned on and the OUT LED turns on green.
  • Page 11: Led And Status Indications

    LED and Status Indications The LEDs on the Energy Pack indicate its status. Energy Pack Status LEDState Green, Input power is applied and within the solid specified range. Red, Input power is outside the specified solid range. Input power is not applied. Green, CapPack Charging in progress.
  • Page 12: Led Indications: Special Cases

    LED Indications: Special Cases All LEDs blinking in unison: See Firmware Updates, page 12. Energy Pack Status Bit Operation As shown in the table below, a CPU application program can automatically monitor the status of the attached Energy Pack via %S0014 (PLC_BAT) and %SA0011 (LOW_BAT).
  • Page 13: Replacing The Cappack Module

    Replacing the CapPack Module The CapPack can be removed and replaced while power is applied to the Energy Pack (hot swapped.) CAUTION When hot swapping CapPacks, do not cycle power until the new CapPack is fully charged and operational. Cycling power before the STAT LED on the CapPack is solid green can result in Controller memory not being preserved.
  • Page 14: Firmware Updates

    because this could result in Controller memory not being preserved. The Energy Pack LEDs and the Controller status bits indicate when charging is complete and the Energy Pack is ready to support backup. To remove a Failed Battery fault and clear the battery status bits, clear the Controller fault table.
  • Page 15: Additional Information

    Additional Information PACSystems RX7i and RX3i CPU Reference Manual, GFK-2222Y or later PACSystems Controllers: Battery and Energy Pack Manual, GFK-2741E or later PACSystems RX3i / Series 90-30 Installation and Maintenance Requirements, GFK-2975 For user manuals, product updates and other information go to the Support website, www.geautomation.com and refer to Controllers and IO, RX3i Rackless Controllers.
  • Page 16 Contact Information Americas: 1-800-433-2682 or 1-434-978-5100 Global regional phone numbers are available on our web site www.geautomation.com ©2016-2018 General Electric Company. All Rights Reserved *Trademark of General Electric Company and/or its subsidiaries. All other trademarks are property of their respective holders. GFK-3000A...