The RX3i CPUs with CPExxx designation (CPE305, CPE310, CPE330 and CPE400)provide an embedded Ethernet
interface for programmer communications. This chapter describes user features and provides basic installation
and startup procedures for this interface.
Ethernet Interface Controls and Indicators
Module Installation
Connection to a 10Base T/100Base Tx Network (all CPExxx) or to a 1000Base T (CPE330 and CPE400
only)
Pinging TCP/IP Ethernet Interfaces on the Network
Note:
CPE330 Release 8.60 provides support for EGD Class 1. PME 8.60 SIM5 is required to
support EGD on both LAN1 and LAN2. All CPE400 releases support this feature.
Note:
Effective with RX3i CPE310/CPE305 Firmware Release 8.30, the CPU itself also supports
EGD
Class 1. Prior to that firmware release, EGD was only available in the RX3i via the
3
RX3i Ethernet Interface module (ETM001).
Note:
For features, installation and startup of the RX3i rack-based Ethernet module (ETM001),
see Chapter 3.
2.1

RX3i Embedded Ethernet Interface Indicators

The Ethernet port has two LED indicators, 100 and LINK. The 100 LED indicates the network data speed (10 or
100 Mb/sec). This LED is lit if the network connection at that network port is 100 Mbps.
The LINK LED indicates the network link status and activity. This LED is lit when the link is physically connected.
It blinks when traffic is detected at that network port.

Ethernet Port LEDs Operation

CPE305/CPE310 Ethernet LED Operation
LED
LED State
On
100
LINK
Proficy Machine Edition Release 8.50 SIM 7 is required for EGD on Embedded Ethernet interface of
3
CPE305/CPE310.
GFK-2224Q
Blinking
Off
On, Green
Off
On, Amber
Blinking, Amber
Off
January 2017
Ethernet Port State
Network data speed is 100 Mbps.
Network data speed is 10 Mbps.
The link is physically connected.
Traffic is detected at the port.
The Ethernet port is not physically connected.