Dlp-L9 Mounting The Ncs 2006 Shelf On A Rack (One Person) - Cisco NCS 2006 Hardware Installation Manual

Ncs 2000 series
Table of Contents

Advertisement

Mounting the Cisco NCS 2006 Shelf
To comply with EN50121-4:2006 - Railway applications, Electromagnetic compatibility, a shielded
Warning
cable must be used to connect to the EMS port. This cable must be less than 30 meters in length and
not placed in the 3 meter boundary, as defined in EN50121-4:2006, Table 2, note 1. Statement 8010
Warning
To comply with EN50121-4:2006 - Railway applications, Electromagnetic compatibility, DC power
cables must be less than 30 meter long. Statement 8011
During installation, do not use the door to handle the chassis.
Note
Note
Remove the door from the NCS 2006 shelf and reinstall it after installing all the other modules.
Procedure
Complete the necessary task as applicable:
Stop. You have completed this procedure.

DLP-L9 Mounting the NCS 2006 Shelf on a Rack (One Person)

Purpose
Tools/Equipment
Prerequisite Procedures
Required/As Needed
DLP-L9 Mounting the NCS 2006 Shelf on a Rack (One Person) , on page 191
DLP-L10 Mounting the NCS 2006 Shelf on a Rack (Two People) , on page 193
DLP-L11 Mounting Multiple NCS 2006 Shelves on a Rack , on page 195
DLP-L9 Mounting the NCS 2006 Shelf on a Rack (One Person)
This task allows one person to mount the shelf on a
rack.
In an ANSI rack, the chassis can be installed
Note
in the front or the middle position. In an
ETSI rack, the chassis is installed only in the
front position.
• # 2 Phillips Dynamometric screwdriver
• ANSI —Six #12-24 x ¾ pan-head Phillips
mounting screws
• ETSI—Six M6 mounting screws
NTP-L2 Mounting the Brackets in ANSI
Configuration , on page 163
As needed
Cisco NCS 2000 Series Hardware Installation Guide
191