Mounting the Cisco NCS 2002 Shelf

This chapter explains how to mount the the NCS 2002 Shelf.
The sections are:

ANSI Rack Installation

The NCS 2002 shelf is mounted on a 19-inch (482.6-mm) or 23-inch (584.2-mm) equipment rack. Make sure
that the correct type of 19-inch ANSI rack is used for mounting the NCS 2002 shelf. If the shelf is mounted
in the front position, then it projects 1.7 inches (43.18 mm) from the front of the rack. If the shelf is mounted
in the middle position, then it projects 5.1 inches (129.54 mm) from the front of the rack. The shelf mounts
in both Electronic Industries Alliance (EIA) standard and Telcordia-standard racks. The shelf is a total of 17.2
inches (431.8 mm) wide with no mounting ears attached. Ring runs are not provided by Cisco and might
hinder side-by-side installation of shelves where space is limited.
The NCS 2002 shelf measures 3.5 inches (88.9 mm) high, 19 or 23 inches (482.6 or 584.2 mm) wide (depending
on which way the mounting ears are attached), and 11.1 inches (304.8 mm) deep.
ANSI Rack Installation, page 61
ETSI Rack Installation, page 62
Wall Mounting the NCS 2002 Shelf, page 65
NTP-L42 Installing the NCS 2002 Shelf, page 65
6
C H A P T E R
Cisco NCS 2000 Series Hardware Installation Guide
61