CHAPTER 4 - INSTAllATION INSTRUCTIONS
to determine the factory configured operating mode. The operating
mode can be reconfigured easily using a computer attached to the
Engineering Port. Contact Honeywell Analytics or your local agent for
more information.
Note: With software versions prior to 1V6, the analogue output signal
may not properly reflect the sensor signal when the sensor signal
is outside the normal measuring range.
The analogue outputs can be connected to voltage input device (eg.
chart recorders) by including an external sense resistor in series with
each loop and connecting the device input in parallel with the resistor.
ie. Use a 100 ohm resistor and select an input range of 2V on the chart
recorder.
The recommended connections are:
Quad Relay
Interface Connections
Quad Relay Interface Card
Programmable
Four Channel Control Card Fitted with:
logic
Controller
Analogue Output Module (Sink) 04200-A-0145
+24V
(18V to 40V)
0V
Isolated Analogue Output Connection with Power Sourced from
Programmable logic Controller Using Sink Module
Channel
Analogue
Output
1
29
2
30
3
31
4
32
Analogue 24V
Analogue Channel 1
Analogue OV
4-43
5704 Control System
Power Supply
0V
24V
28
27
28
27
28
27
28
27
05704-A-0121
27
29
28