12.5 Commissioning Mode for MCS
Sensors
MCS sensors incorporate an internal delay
(approx 10 minutes) when they are set to
sensitivity level L4 or L5. The latter is the
default, thus to enable these sensors to be
commissioned a test mode can be invoked
which sets them to L3 for a defined time. This
option is only available if MCS sensors are
configured on the loops. It is accessed at
level 3 from the Test menu:
1 Select Commissioning Mode ON.
2 Enter the required time in hours.
The Test tab then displays the time remaining
until the end of Commissioning Mode, at which
all MCS sensors revert to their programmed
Alarm sensitivity level. To end Commissioning
Mode before this time, display the Test tab and
press
and then confirm the cancellation.