IF CELL, ZONE OR
PANEL:
IF SPECIFIED PANEL:
Multiple zone co-incidence: for the
Control Matrix entry to be valid,
the number of co-incident zones
must not exceed the chosen zone
Honeywell, Issue 9
March 2007
range.
64
XLS80e Fire Alarm Control Panels
1 Select one of 'Cell, Zone or Panel' (go to
step 2), 'Specified Individual Device'
(step 7), or 'Virtual Input Point' (step 10).
2 If 'Cell, Zone or Panel' is selected, you are
then prompted for a specific panel (Step 3)
or ANY panel for an input.
3 If 'Input from SPECIFIED Panel' is selected,
you are asked to specify a particular panel
number. The * and initial cursor position
indicate the local panel. The * remains fixed,
the cursor is movable. Select a panel from
the list.
4 If the current panel is selected specify
whether the Control matrix rule is to apply
for Normal or Fallback network operation.
5 Select ZONE or PANEL or CELL.
Note: If no cells are configured (Sections
5.1.2.2/5.1.4.2) the ZONE or PANEL/
CELL selection screen is bypassed.
SELECTION OF EITHER NETWORK OPTION
AT STEP 4 OR IF 'ANY' WAS SELECTED AT
STEP 2, DISPLAYS THE FOLLOWING
SCREENS:
Zone Coincidence
6 These options are provided if the input is
from Any Zone or from a range of zones.
They are intended for use with the
Extinguishing System, although are
available for any 'Alarm' input. Select the
required option. SINGLE Zone and 2 Zones
are always available; the remaining options
are only displayed if they are configured in
the panel settings (Section 11.21). In the
illustration, 'n', 'p' and 'q' each represent a
number in the range 3-99.
The use of zone coincidence and
restricted-by-type in the same
Control Matrix entry is not
supported.