Honeywell XLS80e Manual page 64

Panel configuration
Table of Contents

Advertisement

XLS80e Fire Alarm Control Panels
Inputs at a panel on the network
Relationships can be defined between inputs
at one panel and outputs at another panel.
Outputs are applied only at the panel which
directly controls them (as stand-alone panels),
but inputs may be defined as originating at a
different panel. To relate an output operation
on a device supervised by one panel to an input
originating at another, the Control Matrix must
be edited at the panel which supervises the
device.
Note:For Network inputs, the definition of
'Device Coincidence' depends upon the
definition of the input:
Input
Specified zone on
another panel
Any zone on
any panel
57
Device Coincidence
Two sensors in alarm
in the specified zone
Two sensors in alarm
anywhere in the
network (including on
different panels)
Honeywell, Issue 9