Honeywell XLS80e Manual page 75

Panel configuration
Table of Contents

Advertisement

IF OPTION 6 (EXTINGUISHING SYSTEM) IS
CHOSEN:
SELECT THE OUTPUT DEVICE
IF OPTION 6 (OTHER EVENTS) IS CHOSEN, SUB-
MENU IS DISPLAYED:
Honeywell, Issue 9
March 2007
XLS80e Fire Alarm Control Panels
7.6.1.6 EXTINGUISHING SYSTEM
The Extinguishing System input requires a
system number to be specified, i.e. the same
number as the corresponding Control Matrix
output action. Up to 32 Systems can exist on
the panel. See Section 7.8 Extinguishing
System Function for further information.
Select whether the output action is to occur
before or after the delay configured in the
Control Matrix output statement. BEFORE
DELAY does not override the delay; it allows
an output to be activated before the timer
expires (e.g. use for warning lamps, sounders,
and the directional valve). Use AFTER DELAY
for the releasing valve.
The only output for this input category is
'Specified Individual Module'.
EN
EN
This product is not compliant
12094-1
12094-1
!
!
Fire extinguishing installations in
Europe are required to be certified as
compliant to this standard.
7.6.1.7 OTHER EVENTS
The EVACUATE Pushbutton, RESET
Pushbutton, SILENCE SOUNDERS Pushbutton,
Manual Call Point in WALK TEST and TRUE
input options do not require any further definition
(except that EVACUATE can be from 'Any' panel
or from a specified panel); when they are
selected the next display is the OUTPUT options.
The TRANSFER FLAG input requires a flag
number to be specified, i.e. the same number
as the corresponding Control Matrix output
action.
68
CAUTION:
with EN 12094-1.
EN54-2: 9.1.2
Use of TRUE to
disable is not
allowed.