11.8 Loop Options

This setting sets various parameters
associated with the loops. To set these options:
To set these options (confirm changes):
1 Set the signal degraded monitoring period
within the given range. For each device, the
system counts the number of corrupted
responses within the time, and issues the
'Signal Degraded' fault message if the
number exceeds a pre-determined limit.
2 Set the loop start-up boost period within the
given range. During this time the loop is
boosted to turn on all isolators.
3 If the panel is on a Master/Slave network
and with lightly loaded loops and non-
mechanical isolators, and if disablement or
fault network messages are being delivered
slowly during alarm, reduce the boost period
to reduce the loop break recovery time.
4 If spurious duplicate addresses are detected,
then after all real duplicate address faults
are fixed, the spurious detections can be
suppressed. This applies to all panels on
an XLSnet.
5 If spurious TX hard faults are detected the
confirmation time can be increased (default
20 seconds). Applies to local panel only.
Fault confirmation time must not

11.9 Panel Functions

This manual describes the panel functions when
the Panel Functions option is set to Standard.
Ensure that the panel setting is set to the required
function.
Select the type of zone numbering to be used;
either PANEL (local zones) or NETWORK
(network zones).
The number of devices in a network zone is
restricted to 99. Each device is given a
reference number (range 1 to 99) within its
zone. If devices have already been configured
using local zones prior to Panel Functions
being configured for network zones, the panel
provides the option (see below) to automatically
configure the reference numbers and re-configure
zone numbers if they exceed the restriction.
97
EN54-2: 8.1.3
exceed 100 seconds.
Honeywell, Issue 9
March 2007