Earthing And Earth Fault Protection; Running The Motor; Warning Symbols; Motor Run Check List - Honeywell NX series User Manual

Nx series constant and variable torque variable speed drives for induction motors
Hide thumbs Also See for NX series:
Table of Contents

Advertisement

1
8(86)

1.3 Earthing and earth fault protection

The NX frequency converter must always be earthed via a conductor connected to the earthing
terminal
.
The earth fault protection inside the frequency converter protects only the converter itself against
earth faults in the motor or the motor cable.
If fault current protective switches (e.g. RCD or Earth Leakage devices) are to be used in
conjunction with the frequency converter, they must be tested with earth fault currents that are
possible to arise in fault situations.

1.4 Running the motor

Warning symbols

For your own safety please pay special attention to the instructions marked with the following
symbols:
= Dangerous voltage
= General warning
WARNING

MOTOR RUN CHECK LIST

WARNING
Before starting the motor, check that the motor is mounted properly
1
and ensure that the machine connected to the motor allows the
motor to be started.
Set the maximum motor speed (frequency) according to the motor
2
and the machine connected to it.
Before reversing the motor shaft rotation direction make sure that
3
this can be done safely.
Ensure that no power correction capacitors are connected to the
4
motor cable.
Ensure that the motor terminals are not connected to mains
5
potential.