Result after resetting to factory settings
The following table provides an overview of the contents of the memory objects after the
reset to factory settings.
Table 15- 2
Result after resetting to factory settings
Memory object
Actual values of the data blocks, instance data blocks
Bit memories, timers and counters
Retentive tags of technology objects
(e.g. adjustment values of absolute encoders)
Entries in the diagnostics buffer
IP address
Device name
Counter readings of the runtime meters
Time of day
System updates and firmware updates are retained when the CPU is reset to factory settings.
If there was a SIMATIC Memory Card inserted in the CPU prior to the reset to factory settings,
the CPU downloads the configuration on the SIMATIC Memory Card (hardware and software).
A configured IP address is then valid again.
Note
Password for protection of confidential configuration data
The password for protection of confidential configuration data is retained after the CPU is
reset to factory settings. The password is only deleted when the "Delete password for
protection of confidential PLC configuration data" option is set in STEP 7.
You can find additional information on the password for protection of confidential
configuration data in the Communication function manual
(https://support.industry.siemens.com/cs/ww/en/view/59192925).
Additional information
Additional information on "Reset to factory settings" can be found in the Function Manual
Structure and use of the CPU memory
(https://support.industry.siemens.com/cs/ww/en/view/59193101) in the section on memory
areas and retentivity, and in the online help for STEP 7.
SIMATIC Drive Controller
System Manual, 11/2023, A5E46600094-AD
Contents
Initialized
Initialized
Initialized
Initialized
Depends on the procedure:
Using mode switch: is deleted
Using STEP 7: Depending on the setting of the "Keep IP ad-
dress"/"Delete IP address" option buttons
Is set to "CPU"
Initialized
Is set to "00:00:00, 01.01.2012"