2.2.2

SITOP BAT1600

The power cables to the UPS module and to additional battery modules are connected at
power terminals ①. Refer to the diagram in Section "SITOP BAT1600 (Page 22)". The data
cables to the UPS module and to additional battery modules are connected at communication
terminals ②. See also Chapter Installation (Page 211).
Figure 2-11
NOTICE
Material damage
It is not permissible that the "+" and "-" power terminals are connected to the "0V", the 0V
busbar or "GROUND".
Note
Use cables with the same length and the same cross-section.
Dimension the power cables corresponding to the fuse in the battery module.
The fuse should only be inserted in the fuse holder when commissioning the device.
See Connecting SITOP BAT1600 battery modules to the UPS module (Page 213)
Connections and terminal designations
① Power terminals "-" and "+"
② Communication terminals "COM2", "COM1"
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76
Power terminals ① / communication terminals ②
Description, device design, dimension drawing
2.2 Connections and terminal designation
Plug-in terminal each with a screw connection
Plug-in terminal each with a screw connection
31