Troubleshooting
Error
Ex-
Severity
Type
tend-
ed
Error
Type
256
22
MR
256
23
MR
256
24
MR
256
25
MR
256
26
F
256
27
F
257
1
MD
257
2
MR
257
3
MR
257
4
MR
257
5
MD
257
6
MR
257
7
MD
257
8
N
257
9
N
257
10
MR
257
11
N
257
12
N
257
13
MD
257
14
N
257
15
MD
257
16
MR
257
17
F
257
18
F
257
19
MR
182
Alarm Text
Wrong device ID
Corrupt data record
Wrong update
Too much data
Device failure
No boot loader available
Buffer mode is not possible
Device temperature critical
(too high)
Device temperature critical
(too low)
High-resistance connection
to battery
Power supply to at least one
battery interrupted
Unknown battery
Overcurrent
Reset buffer timer
UPS1600 off
Output switched off
Output switched on
obsolete from V2.3
Reset executed
Battery test is negative
Software update successful
Input voltage is too high
Surplus battery
UPS1600 parameters cor-
rupt
Device overtemperature
Capacity test
Help Text
An attempt was made to update the software with an update
file that is not suitable for the UPS1600.
Error during software update - try to update the software again
An attempt was made to update the software with an invalid
update file. The update file is probably too old.
An entry in the software update cannot contain more than
32 bytes of reference data.
Device failure
No boot loader available
Buffer mode not possible - check cabling, fuse and battery
voltages
Device temperature higher than 100 °C. Caution: The highest
permitted temperature could be exceeded!
Device temperature less than -10 °C. Device could leave the
operating range.
High-resistance connection to battery - check battery power
cable
Connection to battery interrupted - check connection and fuse
Data from the battery cannot be read correctly. Battery is defec-
tive or not supported by SIEMENS.
Output current of UPS1600 is too high. Output is switched off
for 20 s. The output is switched on again after 20 s.
PC is shutting down
UPS1600 off - buffer time exceeded.
The UPS1600 output was shut down as result of executing an
instruction or an error situation (e.g. overtemperature, exces-
sive output current).
The UPS1600 output was switched on again as result of execut-
ing an instruction or the correction of an error situation.
Input voltage at UPS1600 was OK again before the buffer time
expired. Connected devices are reset by switching off the
UPS1600 outputs for the configured time.
A cyclic battery test will be performed
Remark:
For firmware versions from V2.2 - and for versions V2.0.× from
version V2.0.5, the alarm is deactivated.
Previous software update was successful - UPS1600 is opera-
tional again.
Input voltage exceeds 30 V. UPS1600 is not operational.
More than 6 batteries are connected. Connect max. of
6 batteries to the Energy Storage Link.
UPS1600-parameters corrupt - try to update the software.
Output and battery charging is switched off to prevent damage
to the device.
Capacity test being performed
Equipment Manual, 07.2021, A5E37775406-11-76