Table of Contents

Advertisement

3. Select the connection between the controller and SITOP UPS1600.
4. Make the required settings in the "Network data".
5. Double-click on SITOP UPS1600 to display it in the device view.
6. Select the PROFINET-interface.
7. Under "Ethernet addresses" in the inspector window enter the IP address of the
SITOP UPS1600, which was already assigned in theTIA Portal.
You have assigned a controller to the SITOP UPS1600.
3.3.6
Assigning a battery module SITOP UPS1100 to the basic device SITOP
UPS1600
The basic functions of the uninterruptible power supply are available with all of the battery
modules that are compatible with the SITOP UPS1600. The SITOP UPS1100 5 Ah LiFePo
battery is first supported by the UPS1600 with SW version V2.1.
Additional functions are available with the SITOP UPS1100 battery module:
● Automatic detection of the battery module rated values
● Automatic management of up to six battery modules
● Temperature-controlled charging
● Battery fast test
● Diagnostics using the SITOP UPS Manager and the web server
SITOP UPS1600 / UPS1100
Manual, 04.2017, A5E37775406-8-76
Engineering and remote access
3.3 SIMATIC STEP 7 in the TIA Portal
55