Loading The Configuration To The Sitop Ups1600 (Commissioning) - Siemens SITOP UPS1600 Equipment Manual

Hide thumbs Also See for SITOP UPS1600:
Table of Contents

Advertisement

3.5.5

Loading the configuration to the SITOP UPS1600 (commissioning)

In the delivered state, the SITOP UPS1600 has not yet been assigned any IP address and the
DHCP protocol is deactivated.
When the SITOP UPS1600 is first connected with a controller (SIMATIC S7 control), it must be
assigned a device name and an IP address by the controller. A new configuration can be
loaded to the device with STEP 7.
Preconditions
• The SITOP UPS1600 has been correctly connected and linked with the system.
• PG/PC with SIMATIC STEP 7 is connected with the network.
Displaying accessible nodes
Note
If nodes can only be accessed via interposed switches or routers (with protocol conversion),
they are not displayed in the list of the accessible nodes.
1. Click in menu "Target system" on "Display accessible nodes".
The "Accessible nodes" window is opened with the following displays:
– Station
– SITOP UPS1600
The following table shows which information is displayed in the "Object name" column.
Accessible nodes
S7-CPU, PC station
Loading the IO controller for the first time
Once you have configured the SITOP UPS1600 and the station, you must load this
configuration into the IO controller (SIMATIC S7 control system). This is the way that the IO
controller is assigned its configured IP addresses.
Before loading, carry out a consistency test to check the configuration for duplicate
addresses, identical names, etc.
Inform yourself whether the IO controller to be loaded can also be initially loaded via the
PROFINET interface. If not, you must first load the hardware configuration via the MPI
interface .
1. Select in the "Target system > Load" menu.
2. Select the module to be loaded.
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76
Object name
Description
Name of the station
The "Details" view also shows the operating state, module type and, if
available, information from the associated STEP 7 project (station
name, CPU name, system identification).
Engineering and remote access
3.5 SIMATIC STEP 7
99

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents